HomeMy WebLinkAboutSTPUD_Water Pressure Model Letter_1895 Talbot Place_10_28_2026
Date: October 29, 2026
To: Donatella Yelda
Re: 1895 Talbot Place, South Lake Tahoe, CA 96150
Pursuant to your request, the South Tahoe Public Utility District (“District”) has prepared the following
information for your use. You will need to consider all other components downstream of the water main
connection including, but not limited to, the extended water service lateral, meters and meter
assemblies, check valves, backflow assemblies, entrance/exit, pipe and fitting losses, etc. Should you
need the length of the service lateral from the main to the meter, we recommend using the width of the
right-of-way due to the unknown location of any future main replacements. The flows and pressures
shown on the attachment are an indication of the existing system conditions at the water main during
maximum day demand and do not include any additional demands from your project.
The estimated static water pressure at your likely point of connection is 31 psi (assuming an elevation of
6539’ MSL at the meter location based on Google Earth). This static pressure is based on the low end of
a range of pressures calculated by a 72-hour maximum day demand extended period simulation
performed using the District’s hydraulic model.
Water flow estimates are provided from the closest existing fire hydrant locations as shown in Figure 1
on the attachment (FH #0820 and FH #3736). The flow estimates and associated pressures are calculated
using the District’s steady-state fire-flow model which has set parameters for various pumps being on/off
and may differ from the boundary conditions associated with the Extend Period Simulation used to
calculate the static pressure provided above. The model calculates the f low estimates at a point on the
pipe in the street at the approximate location of the fire hydrant lateral and does not take into account
any other downstream losses in the lateral, in the hydrant, etc.
The District’s hydraulic model estimates that the water system can provide approximately 480 gallons
per minute while maintaining 20 psi residual pressure near the subject property under the modeled
scenario. This is a modeled estimate and is not a guarantee of flow under all operating or emergency
conditions. The District does not determine the fire flow requirement applicable to property or certify
compliance with the California Fire Code. Those determinations must be made by the applicable fire-
code official.
The water model is an approximate computer representation of the actual distribution system and
should be field verified. Pressure and flow testing at existing hydrants and other locations in your
neighborhood is recommended to verify your system calculations. The District does not provide fire
protection engineering services and does not guarantee flow or pressure. You will need to engage a fire
protection engineer for your system design and have that person evaluate the model data provided
along with pertinent field data to properly design your fire protection system.
The above estimated information regarding water line sizes and water pressure (“Information”) is based
on the District’s currently available water system model, is provided solely in response to your request
for such information, and provided solely to assist you in planning for fire protection purposes in
connection with the development of your property. The water pressure and flows can vary significantly
depending on the time of day, customer utilization, water supply interruption, and water system
operational problems. The Information is provided “as is” without warranty of any kind, and the District
expressly disclaims all express and implied warranties, including, but not limited to, the implied
warranties of merchantability and fitness for a particular purpose, and that the Information is accurate.
The District does not warrant, guarantee, or make any representations regarding the use of, or inability
to use, the Information in terms of correctness, accuracy, reliability, timeliness, completeness, or
otherwise. The entire risk as to the use of the Information is entirely assumed by you. Any person who
uses the information disclaims all liability for damages, costs and expenses and agrees that there are no
remedies against the District and its employees or agents for negligence, or for personal injury, breach of
warranty or contract, including but not limited to indirect, consequential, punitive or incidental damages.
Please contact our direct email at fireflow@stpud.dst.ca.us if you need additional information regarding
pressure or flows for your water service connection.
Sincerely,
Megan Colvey, P.E.
Director of Engineering
South Tahoe Public Utility District
WATER SYSTEM M ODELING BASED ON EXISTING MAX DAY 2014 WATER MODEL
Figure 1 –Schematic map of property location, closest fire hydrants and pipes nearest to service lateral
Table 1 - Steady State Design Fire Flow and Pressure
Fire Hydrant
#
Approximate
Elevation Above
Sea Level (feet)
Static
Pressure1
(psi)
Available Flow at Hydrant
Connection to Main (gpm) at 20
psi Residual Pressure in System
Residual Pressure (psi) at
Hydrant Connection to Main at
1,000 gpm Demand
FH #0820 6539’ 38 4882 n/a
FH #3736 6532’ 41 4493 n/a
1Static pressure provided at the hydrant is based on a steady state model of fire flow demands. This is not
calculated using the same operating conditions as the static pressure provided by the EPS model.
2Residual Pressure at FH #0820 is 29 psi
3Residual Pressure at FH #3736 is 33 psi
FH #0820
1895 Talbot Place
FH #3736
Assumed Point
of Connection